HQL LED ALU PERFORMANCE  5400LM 41W 827 E40

HQL LED ALU PERFORMANCE 5400LM 41W 827 E40

Product benefits
  • Saves up to 78 % energy when used as replacement for mercury vapor lamps (HQL)
  • Low maintenance costs thanks to long lifetime
  • Instant 100 % light, no warm-up time
Areas of application
  • Streets
  • Area lighting
  • Pedestrian zones
  • Parks
  • Outdoor applications only in suitable luminaires
Product features
  • Replacement for HQL: Suitable for operation with conventional control gear (CCG) for HQL or 230 V mains
  • Replacement for other HID: Suitable for operation with line voltage without control gear
  • Power factor: 0.9
  • Type of protection: IP65
  • High surge protection: up to 6 kV (L-N)
  • ENEC-certified safety
Safety advice
  • The bulb may be larger and heavier than the replaced bulb. Before installation it must be checked, if the luminaire and especially the holder is capable of carrying the weight of the lamp. For 90 W types the safety rope included in the packaging needs to be installed.
  • Not suitable for operation with ignitors.
  • Operation on the capacitor can lead to a reduction of the power factor of the system.
  • When installed horizontally, the tc point of the lamp is located on the top side of the lamp.
  • Use in tight luminaires and luminaires with tight reflectors not recommended.
  • All electrical connections must be made by a qualified person.

Product identifiers

SKU: 4099854040764
EAN: 4099854040764
GTIN: 4099854040764
MPN: 4099854040764

Price: £ 67.85 Excl. VAT

Specifications

Lifespan

Lifespan L70/B50 at 25 °C 60000 h
Number of switching cycles 100000
Lumen maintenance at end of service lifetime 0.70
Rated lamp survival factor at 6,000 h ≥ 0.90

Capabilities

Dimmable No

Electrical data

Nominal wattage 41 W
Construction wattage 41.00 W
Nominal voltage 220…240 V
Operating mode CCG, AC Mains
Nominal current 190 mA
Inrush current 16.8 A
Mains frequency 50/60 Hz
Max. lamp number on MCB B10 A - CCG without compensation 26
Max. lamp number on MCB B16 A 52
Max. lamp number on MCB B16 A - CCG with compensation 37
Power factor λ > 0.90

Documents

Documents and certificates

Data sheet
Open

Documents And Certificates

User instruction / safety instructions – HQL LED P
Open
Legal information – Informationstext 18 Abs 4 ElektroG
Open
Legal information – Safety Insert G11201307
Open
Declarations of conformity UKCA – HQL LED E40 E27 Gen6
Open

Photometric And Lighting Design Files

IES file (IES) – HQL LED P 5400LM 41W 827 E40
Open
LDT file (Eulumdat) – HQL LED P 5400LM 41W 827 E40
Open
UGR file (UGR table) – HQL LED P 5400LM 41W 827 E40
Open