Q & A of the Day - Main meter conductors to consumer unit

Published: 3 March 2008 Category: Q&A

Our Voltimum Experts answer your questions on a daily basis in our Technical Expertise area. This one, concerning main meter conductors to the consumer unit, is answered by SELECT:

Q & A of the Day - Main meter conductors to consumer unit
Question: I have recently carried out a periodic test and inspection on a council flat. I noted that the main tails were 16mm, and that the main earth conductor was 10mm and needed upgrading to 25mm main tails and 16mm earth conductor. However. the guy from the council told me it didn't need upgrading and was satisfactory as it was. Could you please advise who is right in this situation. Was I correct in listing it as a defect?

Answer: Such an observation would, in our opinion, warrant a Code 4 observation on the PIR (it does not comply with BS7671 as amended).

To see many more Q & A in Voltimum UK's Experts Area, please click on the link: