Distributor Selection

Select the distributor you would like to use for your shopping cart.

Distributor

SELECT

Q & A of the Day - Should I carry out an earth fault loop impedance test?

Published: 3 February 2011 Category: Q&A

Our Voltimum Experts answer your questions on a daily basis in our Technical Expertise area. This one, about a periodic inspection and test on a large food factory installation, and earth fault loop impedance testing, is answered by SELECT:

Q & A of the Day - Should I carry out an earth fault loop impedance test?
Question: We are currently carrying out a periodic inspection and test on a large food factory, as part of the infrastructure testing.

There are various 110V CTE socket outlets, which are protected by a distribution board having two-pole 16A MCBs fitted. The distribution board is 110V CTE fed from a local 230/110 10kVA transformer.

Apart from measuring the insulation resistance test, R1+R2 and polarity, is there any requirement for carrying out an earth fault loop impedance test for the correct disconnection time?

Answer: For reduced low voltage systems, Table 41.6 from BS7671:2008 should be used for maximum earth fault loop impedances.

To see many more Q & A in Voltimum UK's Experts Area, please click on the link:

www.voltimum.co.uk/consult.php?universe=consult.index.questions