Tristan asks this question, which concerns emergency lighting system testing and the changed requirement for it. It has been answered by Lux Magazine (Theme – Lighting):
This Q & A is one of thousands posted in our Technical Expertise area, and answered on a daily basis by our Voltimum Experts.
Question: I have been told that the old six monthly emergency light testing (1 hour) is no longer required.
Now, we only have to complete one monthly test function and a yearly three-hour test, I gather. Is that right?
Answer: You've been advised correctly. The current minimum requirements are for a monthly function test and an annual full duration test.
To learn more about emergency lighting in general, please go to the website of the Industry Committee for Emergency Lighting (ICEL) at: www.icel.co.uk
To see many more Q & A in Voltimum UK's Experts Area, please click on the link. Experts from leading organisations provide online answers to your technical questions on a broad range of subjects. Our searchable database of existing Q & As now contains over 3,500 entries; you can browse through them here.