Check your cable sheathing – it may not offer the conductor protection you expect.

Published: 12 May 2014 Category: News

Dr Jeremy Hodge, chief executive of the British Approvals Service for Cables (BASEC) advises end users and manufacturers to ensure the quality of cable sheathing before use.

Check your cable sheathing – it may not offer the conductor protection you expect.
Electricians across the UK and Europe should check their cable can be easily stripped before first fix installation. It is a simple and worthwhile check that can save time and cost later. If cable has been laid and plastering or decoration has been completed, when the installer comes to fit accessories at second fix and the cable cannot be stripped easily, there can be serious difficulties which will cost the electrician both time and money.
 
In the cable production process, a sprinkling of fine chalk or a silicone spray is applied in between the cores of a multi core cable, which enables the sheath to be easily stripped from the cores.  If the chalk runs out during production, or an insufficient amount of chalk is used, the sheath will stick to the cores and make the cable difficult or impossible to strip. 
 
Having reviewed this problem with installer organisations and cable manufacturers, BASEC is treating this problem as a serious production failure and is advising manufacturers to be more vigilant in their production. Any cable batches found to have insufficient chalk should not be sold and should be returned to the supplier.
 
Manufacturers are also advised to ensure the thickness of the sheath meets relevant standards. If the sheath is too thin cables can disintegrate when subjected to rigorous safety tests. For example, a cable sheath can fragment and break in a cold bending test if it is too thin.  This problem could result in a fire, short circuit or an electric shock.
 
Strippability can be readily checked by the electrician by feeling the free end of each reel of cable with a fingernail to see if the sheath can be lifted away from the cores. If it will not come away from the cores easily, then normal stripping of the cable should be attempted. If it is difficult to strip without damaging the insulation material, affected cable should be returned to the supplier. Installers should always make checks on each reel of cable used.
 
If cable has been installed and then found to be unstrippable at second fix, the electrician should advise the supplier of the particular cable batches purchased and the problem they have encountered. This should then be investigated by the supplier. With regard to the installation, ideally the problem cable should be replaced. 
 
Electrician’s priority must be to ensure quality and safety. To help safeguard against the risk of installing cable which is substandard, electricians should ensure that the cable supplied is the correctly specified cable and always check the markings on the cable sheath - not just the packaging. For peace of mind, you should also insist on an independent third-party approved cable with a BASEC or HAR mark.  
 
It is important to note that the problem of unstrippable cable can happen with low smoke halogen free cables as well as PVC.
 
Further information about BASEC is available at www.basec.org.uk or you can contact BASEC directly at [email protected] or +44 1908 267300