Our Voltimum Experts answer your questions on a daily basis in our Technical Expertise area. This Question of the Day, concerning a ring main wired in mineral insulated cable, is answered by the NICEIC:
It is self explanatory as to doing R1 and Rn, but there is no way of doing R2, and hence R1 + R2 either.
Answer: R1 + R2 readings can only be reliably proven on an all insulated installation (PVC/PVC wiring). Any installation having metallic sheaths(SWA and MI) and metallic construction(conduit/trunking) can introduce parallel paths.
Therefore, a visual inspection for soundness of the circuit should be carried out, and then either Test Method 1 or 2 carried out thereafter.
Please refer to the On Site Guide (page 78) for further guidance.