This Voltimum UK user asks about what connection method to take in an extra consumer unit in a domestic property. His question is answered by the ECA (Theme – Installation Tips):

Q & A of the Day – What connection for this circuit having an extra consumer unit?
This Q & A is one of thousands posted in our Technical Expertise area, and answered on a daily basis by our Voltimum Experts.

Question: We are to carry out alterations to a domestic kitchen that requires additional circuits. The existing consumer unit is of the re-wirable type, and the customer is reluctant to upgrade it.

We propose to fit a four-way additional consumer unit to accommodate the new circuits. One of the ways will also supply the existing consumer unit with an MCB.

Would it also be a preference to block connect the double insulated tails, as there is an isolator switch present - rather than creating a new circuit through the additional consumer unit?

Answer: Normally, you would use blocks on the tails to feed the new consumer unit - leaving the existing consumer unit as it is.