Q & A of the Day – Is this garage sub-distribution board earth CPC adequate?

Published: 27 April 2012 Category: Q&A

Jamie Harrison asks a question about the earthing of a sub-distribution board. His question has been answered by the ECA (Theme – Regulations & Legislation):

Q & A of the Day – Is this garage sub-distribution board earth CPC adequate?
This Q & A is one of thousands posted in our Technical Expertise area, and answered on a daily basis by our Voltimum Experts.

Question: If one feeds a sub-distribution board, say to an internal garage or workshop and it is say, dependent on the load, a PVC 6mm or PVC 10mm twin & earth cable, is this earth circuit protective conductor (CPC) adequate if all the test parameters are satisfied?

Answer: Normally yes, so long as the equation in 543.1.3 is satisfied and that the required disconnection time is met.

To see many more Q & A in Voltimum UK's Experts Area, please click on the link:

www.voltimum.co.uk/consult.php?universe=consult.index.questions

Answer: Normally yes, so long as the equation in 543.1.3 is satisfied and that the required disconnection time is met.