CP-E 48/0.62 Power supply In:100-240VAC Out: 48VDC/0.62A
The CP-E 48/0.62 is a power supply from the CP-E range. The primary switch mode power supply offers a wide range input of 85-264 V AC and 90-375 V DC, rated input voltage is 100-240 V AC. The rated output power is 30 W, rated output current is 0.625 A at an output voltage of 48 V DC. The output voltage is adjustable within a range of 48 to 55 V DC. The power supply provides a U/I output characteristic and allows parallel operation to enable redundancy.
Product identifiers
SKU: 1SVR427030R2000
EAN: 4016779656917
GTIN: 4016779656917
MPN: CP-E 48/0.62
Loyalty points:
54
Price: £ 107.10 Excl. VAT
Categories
Features
|
Depth
|
114 mm
|
|
Width
|
40.5 mm
|
|
Height
|
90 mm
|
|
EFI00008
|
-
|
|
EFI00040
|
-
|
|
EFI00049
|
-
|
|
EFI00332
|
-
|
|
EFI00846
|
-
|
|
Stabilized
|
yes
|
|
Power output
|
30 W
|
|
Built-in width
|
40.5 mm
|
|
Built-in height
|
90 mm
|
|
Modular version
|
no
|
|
Power consumption
|
35.7 VA
|
|
Short-circuit-proof
|
yes
|
|
Max. output current 1
|
-
|
|
Max. output current 2
|
|
|
Max. output current 3
|
|
|
Wall mounting possible
|
no
|
|
Rated supply voltage DC
|
90 - 375 V
|
|
Direct mounting possible
|
no
|
|
Degree of protection (IP)
|
IP20
|
|
Output voltage stabilized
|
yes
|
|
SIL according to IEC 61508
|
None
|
|
Suitable for rail mounting
|
yes
|
|
Degree of protection (NEMA)
|
1
|
|
Type of electric connection
|
Screw connection
|
|
1st secondary output voltage
|
48 - 48 V
|
|
2nd secondary output voltage
|
|
|
3rd secondary output voltage
|
|
|
Secondary voltage adjustable
|
no
|
|
Rated supply voltage AC 50 Hz
|
85 - 264 V
|
|
Rated supply voltage AC 60 Hz
|
85 - 264 V
|
|
Suitable for safety functions
|
no
|
|
Voltage type (supply voltage)
|
AC/DC
|
|
Nominal value output current 1
|
0.62 A
|
|
Nominal value output current 2
|
|
|
Nominal value output current 3
|
|
|
Nominal value output voltage 1
|
48 V
|
|
Nominal value output voltage 2
|
|
|
Nominal value output voltage 3
|
|
|
Width in number of modular spacings
|
-
|
|
Performance level according to EN ISO 13849-1
|
None
|