TeSys K - differential thermal overload relays - 0.11...0.16 A - class 10A

TeSys K - differential thermal overload relays - 0.11...0.16 A - class 10A

TeSys LRK thermal overload relay, 0.16A/690V, thermal setting range 0.11-0.16A, tripping class 10A, for protection of 3-phase motors less than 0.06kW@400V. Differential device with phase failure and load unbalance detection. It provides a thermal adjustement dial, a manual-automatic reset selector, a test slide switch for simulation of a tripping, reset/stop button, a flag indicator and 2 auxiliary contacts 1NO+1NC for fault signalling. Settings are protected by a transparent cover lockable by sealing. Connection by screw clamp terminals, it connects directly to the bottom terminals of 3-pole contactors LC1K06-K16. Mounting on DIN rail, separated from the contactor, with use of a terminal block LA7K0064 (to be ordered separately). Multi standards certified (IEC, UL, CSA, CCC, EAC),

Product identifiers

SKU: LR2K0301
EAN: 3389110230352
GTIN: 3389110230352
MPN: LR2K0301

V+ Loyalty points:

17

Price: £ 40.63 Excl. VAT

Videos

Promotional video

Specifications

Release class CLASS 10 A
Mounting method Direct attachment
Reset function input no
Adjustable current range
Reset function automatic yes
Reset function push-button yes
Max. rated operation voltage Ue 690 V
Type of electrical connection of main circuit Screw connection
Number of auxiliary contacts as normally open contact 1