Acti9 iC60 RCBO - 4P - 32 A - B Curve - 6000A/6kA - 30 mA - A type

Acti9 iC60 RCBO - 4P - 32 A - B Curve - 6000A/6kA - 30 mA - A type

This Acti9 iC60 is a modular residual current breaker with overcurrent protection (RCBO). It is a 4P RCBO with 4 protected poles, rated current is 32A, and operating voltage is 380VAC to 415VAC. The earth leakage protection class is A type with a sensitivity of 30mA. The earth-leakage protection time delay is instantaneous. Breaking capacity at 280VAC to 415VAC is 6000A according to EN/IEC 61009-2-1 and 6kA according to EN/IEC 60947-2. Its unique Visitrip indicator reduces intervention time by showing the faulty circuit. Its Visisafe green strip guarantees the physical opening of the contacts to allow downstream maintenance. Its fast closing mechanism independent of manual operation improves its service life. This product is compliant with EN/IEC 60947-2 and EN/IEC 61009-2-1 standards. Electrical endurance goes up to 10000 cycles, and mechanical endurance goes up to 20000 cycles. The Ue operational voltage is 380VAC to 415VAC. The Ui rated insulation voltage is 500VAC. The Uimp rated impulse withstand voltage is 4kV. The frequency is 50Hz. It is DIN rail mountable. The width in 9mm pitches is 8. The product color is white (RAL9003). The dimensions are (W) 72mm x (H) 86mm x (D) 78mm. The weight is 423g. It has an IP20 degree of protection. It becomes IP40 once in modular enclosure according to IEC/EN 60529 standard. The operating temperature is from -25°C to 40°C. The storage temperature is from -40°C to 70°C.

Product identifiers

SKU: A9D87432
EAN: 3606481157584
GTIN: 3606481157584
MPN: A9D87432

Voltimum+ Loyalty Programme Loyalty points: 1

Price: £ 449.00 Excl. VAT

Specifications

Frequency 50 Hz
Power loss -
Voltage type AC
Rated current 32 A
Rated voltage 400 V
Built-in depth 45 mm
Pollution degree 2
Rated fault current 0.03 A
Over voltage category 3
Release characteristic B
Number of poles (total) 4
Degree of protection (IP) IP20
Flush-mounted installation no
Disconnection characteristic Undelayed
Width in number of modular spacings 4
Rated impulse withstand voltage Uimp 4 kV
Connectable conductor cross section solid-core
Rated short-circuit breaking capacity according to EN 61009 6 kA
Rated short-circuit breaking capacity Icn according to EN 61009-1 6 kA