Earth fault loop impedance explained: how to test Zs, use BS 7671 maximum values, apply the 0.8 rule, and troubleshoot readings that are too high.
Earth fault loop impedance is the test that proves a circuit will actually disconnect in a fault. Get the reading wrong, or compare it with the wrong figure, and a circuit that looks compliant on the schedule may not clear an earth fault in time. This guide covers how to carry out an earth loop impedance test, how to read maximum Zs values from BS 7671, why a measured reading is compared with 80% of the table value, and what to do when Zs is too high.
This guide is written to BS 7671:2018+A4:2026, published on 15 April 2026. Amendment 4's supporting guidance revised the rationale behind maximum Zs values; the figures below are the Table 41.3 values and the 0.8 site check that follows from them.
The short answer
Zs is the impedance of the earth fault path: the supply (Ze) plus the line and protective conductors of the circuit (R1 + R2). BS 7671 Tables 41.2 to 41.4 give the maximum Zs for each protective device, so that the device disconnects within the required time. Those tables assume conductors at full operating temperature, so a reading taken on a cold circuit should not exceed 80% of the tabulated value. For a 32 A Type B circuit-breaker that means a table limit of 1.37 Ω and a maximum measured reading of about 1.10 Ω.
What is earth fault loop impedance?
When a line conductor faults to earth, fault current flows round a loop: out along the line conductor to the fault, back along the circuit protective conductor (cpc) to the main earthing terminal, through the supply earth path to the transformer, and back through the transformer winding and supply line conductor. The total impedance of that loop is the earth fault loop impedance, Zs.
The lower Zs is, the higher the fault current, and the faster a fuse or circuit-breaker operates. BS 7671 relies on this for automatic disconnection of supply (ADS): the protective device must disconnect quickly enough that touch voltages on exposed metalwork do not persist long enough to cause harm.
Ze, Zs and R1 + R2
Ze is the external earth fault loop impedance: the part of the loop outside the installation, from the origin back to the source.
R1 + R2 is the resistance of the circuit's line conductor (R1) and cpc (R2), measured by a dead continuity test to the furthest point of the circuit.
Zs is the total, found either by direct measurement or by calculation: Zs = Ze + (R1 + R2). Where the circuit is fed from a sub-main distribution board, Ze is replaced by the loop impedance measured at that board (Zdb).
For quick checks of this sum, Voltimum's R1+R2 Zs Calculator works in either direction.
Typical Ze values
Distributors typically declare the following maximum values for supplies up to 100 A, as quoted in IET Wiring Matters. Measured values are usually lower.
Earthing arrangement | Typical maximum Ze | Notes |
|---|---|---|
TN-C-S (PME) | 0.35 Ω | Combined neutral and earth in the supply cable. |
TN-S | 0.8 Ω | Separate earth, often the lead sheath or armour of the supply cable. |
TT | 21 Ω | Excludes the resistance of the consumer's own earth electrode. |
A measured Ze well above these figures points to a problem with the supply earth, and should be reported to the distribution network operator rather than accepted.
Maximum disconnection times
The maximum Zs for a device depends on how fast it must disconnect. Under Regulation 411.3.2 and Table 41.1 of BS 7671, for a 230 V system:
Circuit | TN system | TT system |
|---|---|---|
Final circuits up to 63 A with one or more socket-outlets, and final circuits up to 32 A supplying only fixed equipment | 0.4 s | 0.2 s |
Distribution circuits, and any circuit not covered above | 5 s | 1 s |
Maximum Zs values: where to find them
BS 7671 Chapter 41 gives the limiting values for common protective devices:
Table 41.2: fuses to BS 88-2, BS 88-3, BS 3036 and BS 1362, for 0.4 s disconnection.
Table 41.3: circuit-breakers to BS EN 60898 and the overcurrent part of RCBOs to BS EN 61009-1, Types B, C and D.
Table 41.4: fuses for 5 s disconnection, for distribution circuits and circuits not requiring 0.4 s.
Table 41.5: maximum Zs where an RCD provides fault protection (see below).
Each value is derived from Zs × Ia ≤ Uo × Cmin, where Uo is 230 V, Ia is the current that operates the device within the required time, and Cmin is a voltage factor of 0.95 for a supply given under the ESQCR. For a circuit-breaker, Ia is the instantaneous tripping current: 5 × In for Type B, 10 × In for Type C and 20 × In for Type D. So a 32 A Type B gives 230 × 0.95 ÷ 160 = 1.37 Ω. Manufacturers' data can be used instead where it is available, and Appendix 3 of BS 7671 encourages it.
Table 41.3: maximum Zs for circuit-breakers (0.4 s, 230 V)
Rating (A) | Type B (Ω) | Type C (Ω) | Type D (Ω) |
|---|---|---|---|
6 | 7.28 | 3.64 | 1.82 |
10 | 4.37 | 2.19 | 1.09 |
16 | 2.73 | 1.37 | 0.68 |
20 | 2.19 | 1.09 | 0.55 |
25 | 1.75 | 0.87 | 0.44 |
32 | 1.37 | 0.68 | 0.34 |
40 | 1.09 | 0.55 | 0.27 |
50 | 0.87 | 0.44 | 0.22 |
For Types B and C the same values apply to both 0.4 s and 5 s disconnection, because disconnection is achieved by the instantaneous magnetic trip. Type D has separate 0.4 s and 5 s values in Table 41.3; the figures above are the 0.4 s values.
The 0.8 rule: comparing a measured reading
The Chapter 41 values assume conductors at their maximum operating temperature, typically 70 °C for thermoplastic cables. When you test, the circuit is usually cold, so conductor resistance, and therefore Zs, is lower than it will be under load. Comparing a cold reading directly with the table figure can pass a circuit that would fail when warm.
BS 7671 deals with this in Appendix 3 (Appendix 14 in the 17th Edition, which is why older guidance cites that number) by applying a factor of 0.8. A measured Zs is acceptable where it does not exceed 0.8 × Uo × Cmin ÷ Ia, which is the same as 80% of the tabulated value. As the IET explains in Wiring Matters, this is also why the maximum values in the On-Site Guide and Guidance Note 3 are lower than those in BS 7671: those publications give field values, referenced to an ambient of 10 °C, rather than design values.
Maximum measured Zs for circuit-breakers (0.8 × Table 41.3)
Rating (A) | Type B (Ω) | Type C (Ω) | Type D (Ω) |
|---|---|---|---|
6 | 5.82 | 2.91 | 1.46 |
10 | 3.50 | 1.75 | 0.87 |
16 | 2.18 | 1.10 | 0.54 |
20 | 1.75 | 0.87 | 0.44 |
25 | 1.40 | 0.70 | 0.35 |
32 | 1.10 | 0.54 | 0.27 |
40 | 0.87 | 0.44 | 0.22 |
50 | 0.70 | 0.35 | 0.18 |
These figures are 0.8 × the Table 41.3 values, rounded. Guidance Note 3 and the On-Site Guide tabulate their own measured values at 10 °C, which can differ by a hundredth of an ohm or so, and GN3 Appendix A gives correction factors for testing at other ambient temperatures.
What to write on the schedule
The "maximum permitted Zs" column on the model schedule expects the Chapter 41 value from BS 7671. If you enter a value from another source, such as manufacturer's data or GN3, the notes to the schedule require the source to be stated in the remarks column. Record the measured Zs as measured, and make the 0.8 comparison yourself.
How to carry out an earth loop impedance test
Loop testing is a live test, so it has to be justified and carried out safely. Regulation 14 of the Electricity at Work Regulations 1989 only permits work on or near live conductors where it is unreasonable for them to be dead, and HSE guidance GS38 sets out the test lead and instrument requirements. Use a GS38-compliant multifunction tester, fused leads or a plug-in lead, and appropriate PPE.
Measuring Ze
Ze is measured at the origin, between the line conductor on the supply side of the main switch and the main earthing conductor. To exclude parallel earth paths through bonding and services, the main earthing conductor is disconnected from the main earthing terminal for the test. That means the installation must be isolated first, and the earthing conductor must be reconnected before the supply is restored. Never leave an installation energised with the earthing conductor disconnected.
Determining Zs: calculation or measurement
Regulation 643.7.3.1 requires Zs to be measured or determined by an alternative method. The IET's guidance on minimising unnecessary live testing makes the point that calculation is often the safer choice at initial verification: measure Ze once, measure R1 + R2 for each circuit by dead testing, and add them. That keeps live testing to the origin.
Two points matter when you do this:
Do not work backwards. It is not acceptable to measure Zs and subtract Ze to find R1 + R2, because a measured Zs includes parallel paths that Ze excludes.
Parallel paths lower a measured Zs. Metallic services, containment and structural steel can make a direct Zs reading lower than Ze + (R1 + R2). The calculated figure is the more reliable test of the circuit itself.
A direct live Zs measurement is still useful, particularly at periodic inspection, where it can reveal a high-resistance joint in a busbar, device or accessory that a calculation would miss.
Two-wire and no-trip testing
Two-wire high-current test: a test current of a few amps between line and earth. Accurate and repeatable, but it will trip an RCD or RCBO on the circuit.
Three-wire no-trip test: a low test current, typically around 15 mA, drawn in a way that avoids tripping the RCD. More convenient, but readings can be affected by circuit noise and by the RCD's own coil adding resistance, often called RCD uplift.
Never bypass or link out an RCD to carry out a high-current test. If a no-trip reading looks high or varies between tests, repeat it, check the instrument's specified accuracy at low impedance, and confirm with a two-wire test where the circuit can be tested without an RCD in circuit, or by calculation from Ze and R1 + R2.
RCD-protected circuits and TT systems
Where an RCD provides fault protection, disconnection time depends on the RCD rather than the fault current, so a much higher Zs is permitted. Two sets of figures are often confused:
Table 41.5 gives maximum Zs values based on a 50 V touch voltage: 1,667 Ω for a 30 mA RCD, 500 Ω for 100 mA, 167 Ω for 300 mA and 100 Ω for 500 mA. For TT systems, Regulation 411.5.3 requires RA × IΔn ≤ 50 V.
Regulation 411.4.4 for TN systems works from Uo rather than 50 V, which gives about 7,283 Ω for a 30 mA RCD. Table 41.5 may be applied instead under Regulation 411.4.204.
Neither figure is a design target. On a TT system the note to Table 41.5 warns that an electrode resistance above 200 Ω may not be stable. On a TN system, a Zs well above the Table 41.3 value on an RCBO-protected circuit is still worth investigating: it usually means a poor connection or a long, small cpc, and the overcurrent part of the RCBO may not clear a fault in time on its own. Regulation 643.7 also allows that, once the effectiveness of RCD protection has been confirmed at a point downstream of the RCD, the installation beyond that point may be verified by confirming continuity of the protective conductors.
Worked examples
32 A ring final circuit, TN-C-S
Ze measured at 0.30 Ω. End-to-end ring tests give a cross-connected (R1 + R2) of 0.55 Ω. Calculated Zs = 0.30 + 0.55 = 0.85 Ω. The circuit is protected by a 32 A Type B RCBO, so the maximum measured value is 1.10 Ω (0.8 × 1.37). The circuit complies.
20 A radial to an outbuilding, TN-S
Ze measured at 0.60 Ω. The circuit is 30 m of 2.5/1.5 mm² flat twin and earth, and R1 + R2 is measured at 0.59 Ω, close to the tabulated 19.51 mΩ/m at 20 °C. Calculated Zs = 0.60 + 0.59 = 1.19 Ω.
With a 20 A Type B device, the maximum measured value is 1.75 Ω. Complies.
With a 20 A Type C device, the maximum measured value is 0.87 Ω. Does not comply on overcurrent protection alone.
To run these sums for your own circuits, use the R1+R2 Zs Calculator. The second case is common when a Type C device is fitted for inrush without checking Zs. For supplies to garages and outbuildings, see How to Wire a Garage Consumer Unit.
When Zs is too high
Split the problem first: measure Ze at the origin. If Ze is high, the issue is the supply earth or the main earthing conductor. If Ze is normal, the issue is in the circuit.
Likely cause | What to check or do |
|---|---|
High Ze | Check the main earthing conductor, its connections and the earth clamp. Report an abnormally high Ze to the distribution network operator. |
Loose or high-resistance connection | Check terminations at the device, accessories and joints on the cpc. A single poor joint can add several tenths of an ohm. |
Long circuit or small cpc | Reduce the circuit length, increase the cable or cpc size, or re-route the circuit. |
Wrong device type | A Type B device has a much higher maximum Zs than Type C or D. Only change type where the load allows it. |
No alternative protection | Fit RCD protection (for example an RCBO) for fault protection, and check the cpc remains adequately sized for the fault energy. |
On a periodic inspection, a Zs above the limit is recorded as an observation on the EICR, with a code reflecting the risk. Whatever the remedy, remember that Zs also governs thermal protection of the cpc: a lower fault current means the device takes longer to disconnect, so the adiabatic check of Regulation 543.1.3 still applies.
Frequently asked questions
What is the maximum Zs for a 32 A Type B MCB?
Table 41.3 of BS 7671 gives 1.37 Ω for a 32 A Type B circuit-breaker at 230 V. A reading measured on a cold circuit should not exceed about 1.10 Ω, which is 80% of the table value.
Why do I multiply maximum Zs values by 0.8?
The BS 7671 tables assume conductors at full operating temperature. A circuit tested cold has lower resistance, so Appendix 3 of BS 7671 applies a factor of 0.8 to allow for the rise in resistance when the circuit is loaded.
Can I calculate Zs instead of measuring it?
Yes. BS 7671 allows Zs to be measured or determined by an alternative method. Adding a measured Ze to the measured R1 + R2 of the circuit is an accepted method and reduces live testing. Do not measure Zs and subtract Ze to find R1 + R2.
What is the maximum Zs for a circuit protected by a 30 mA RCD?
Table 41.5 of BS 7671 gives 1,667 Ω for a 30 mA RCD, based on a 50 V touch voltage. This is not a design target, and on a TT system an earth electrode resistance above 200 Ω may not be stable.