Q & A of the Day – What are the earthing requirements for using SY cable on single- or three-phase extension leads?

Published: 6 May 2016 Category: Q&A

James asks this question, which is about the earthing requirements for using SY cable. It has been answered by the NICEIC (Theme – Cables, Wiring and Wiring Accessories):

Q & A of the Day – What are the earthing requirements for using SY cable on single- or three-phase extension leads?

This Q & A is one of thousands posted in our Technical Expertise area, and answered on a daily basis by our Voltimum Experts.

Question: Can you please tell me the requirements for using SY cable on a three-phase or single-phase extension lead?

I use use one cable core for the earth and also bond the braiding, making a pigtail at the plastic sleeved ends. Some people cut the braiding short and just tape it up.

So can you tell me the correct method, as there doesn't seem to be a regulation on the subject?

Answer: We would always recommend using the correct gland for the cable in line with the manufacturer's instructions. There are glands on the market designed for SY control cables.

The galvanised braid is not considered suitable to use as a circuit protective conductor (CPC) for the cable, and it is also not considered to be an exposed conductive part.

The reason why it is not considered an exposed conductive part is that the cable meets the requirements of Regulation 412.2.4.1 of BS 7671 for protection against electric shock by means of the protective measure of double or reinforced insulation.

To see many more Q & A in Voltimum UK's Experts Area, please click on the link. Experts from leading organisations provide online answers to your technical questions on a broad range of subjects. Our searchable database of existing Q & As now contains over 3,500 entries; you can browse through them here.