Q & A of the Day - How do I set a DOL starter motor overload relay?

Published: 11 April 2011 Category: Q&A

Our Voltimum Experts answer your questions on a daily basis in our Technical Expertise area. This one, concerning an induction motor overload relay and its setting, is answered by ABB:

Q & A of the Day - How do I set a DOL starter motor overload relay?
Question: How do you set the motor overload relay for a Direct Online (DOL) starter for an induction motor? Is there a factor/term that one can multiply the full load current by, in order to set it (slightly above) the full load current?

Answer: The overload should be set to the motor rating plate full load current. There is no factor applied to the set point for DOL starting. Any factoring to allow for starting currents or overload situations during running is allowed for within the overload relay itself.