Our Voltimum Experts answer your questions on a daily basis in our Technical Expertise area. This Question of the Day, concerning fire alarm panel LV supply segregation, is answered by the ECA:
The ELV fire alarm wiring is to be installed onto a basket system at least 300mm away from the general LV wiring. Can I install the supply cable in the same basket as the ELV fire alarm cables or can it go in with the general LV wiring? Or, should it be segregated from both the general LV wiring and the ELV fire alarm wiring? This fire alarm system will be wired using Red FP '200' on both LV and ELV.
Answer: It is good practice to segregate ELV cables from LV cables. However, where the fire alarm system ELV cables have an integral screen and the same rating as the LV cables, they can be run on/in the same containment. However, I do recommend that you check your client's specification - if one exists.
To see many more Q & A in Voltimum UK's Experts Area, please click on the link:
https://www.voltimum.co.uk/consult.php?universe=consult.index.questions