Miniature circuit-breaker, Acti9 iC40N, 1P+N, 25 A, B curve, 6000 A (IEC 60898-1), 10 kA (IEC 60947-2) Zoomed Image
Schneider Electric

Miniature circuit-breaker, Acti9 iC40N, 1P+N, 25 A, B curve, 6000 A (IEC 60898-1), 10 kA (IEC 60947-2)

This Acti9 iC40N product is a low voltage miniature circuit breaker (MCB). It is a 1P+N circuit breaker with 1 protected pole and 25A In rated current and B tripping curve. The rated short circuit breaking capacity goes up to 10kA at 230VAC conforming to EN/IEC 60947-2 standard and 6000A at 230VAC conforming to EN/IEC 60898-1 standard. This product complies with both industrial standard EN/IEC 60898-1 and residential standard EN/IEC 60947-2. This miniature circuit breaker combines functions of circuit protection against short circuit and overload current, control and isolation. The installation and cabling are simplified with clip on function as well as ease of maintenance. It has an electrical endurance going up to 10000 cycles and a mechanical endurance going up to 20000 cycles. The Ue operational voltage is 230VAC. The Ui rated insulation voltage is 400VAC. The Uimp rated impulse withstand voltage is 4kV. The operating frequency is 50Hz or 60Hz. It can be mounted on DIN rail for modular installation. Its width is 2 pitches of 9mm. Pollution degree is 3. The product colour is white (RAL9003). The dimensions are (W) 18mm x (H) 85mm x (D) 74mm. The weight is 120g. According to IEC 60529 standard, the degree of protection is IP20 and IP40 in enclosure. The operating temperature is -25°C to 70°C. The storage temperature is -40°C to 85°C.

Product details

SKU Code: A9P44625

EAN Code: 3606481324559

Minimum order: 1

Available for Back Order (1 seller)

Availability

Farnell

Back Order Manufacturer lead time of 5 weeks.

£53.29

Distributor Availability Price  
Farnell Back Order Manufacturer lead time of 5 weeks. £53.29 Ex. VAT

19 loyalty points

Price:

£53.29 ex. vat

Technical Data

Main Features

Built-in depth

44 mm

Frequency

Rated insulation voltage Ui

400 V

Number of poles (total)

2

Width in number of modular spacings

1

Number of protected poles

1

Rated short-circuit breaking capacity Icn according to EN 60898 at 400 V

-

Rated short-circuit breaking capacity Icu according to IEC 60947-2 at 230 V

10 kA

Additional equipment possible

TRUE

Rated short-circuit breaking capacity Icn according to EN 60898 at 230 V

6 kA

Rated impulse withstand voltage Uimp

4 kV

Degree of protection (IP)

IP20

Rated current

25 A

Rated voltage

230 V

Release characteristic

B

Concurrently switching neutral conductor

TRUE

Flush-mounted installation

FALSE

Voltage type

AC

Explosion-proof

FALSE

Rated short-circuit breaking capacity Icu according to IEC 60947-2 at 400 V

-

Connectable conductor cross section solid-core

Over voltage category

3

Ambient temperature during operating

Current limiting class

3

Connectable conductor cross section multi-wired

Pollution degree

3

Power loss

4.3 W

Downloads