QOvs - earth leakage circuit breaker - 1P + Ns - C curve - 20A - 30mA

QOvs - earth leakage circuit breaker - 1P + Ns - C curve - 20A - 30mA

This QOvs is a modular residual current breaker with overcurrent protection (RCBO). It is a 1P+Ns circuit breaker with 1 protected pole, 20A In rated current and C tripping curve. The earth leakage protection class is AC type with a sensitivity of 30mA. The earth-leakage protection time delay is instantaneous. The Icn rated short circuit breaking capacity is up to 10000A according IEC 61009-2-2 standard. This product protects against short circuit, cable overload, electrical shock by indirect contact and fire hazards. It has a plug on system for fast and easy installation, no conneciton errors and more safety. It also has an operating test button on the front panel. This product is compliant with IEC 61009-2-2 and IEC 61009-1 standards. It has an electrical endurance going up to 5000 cycles and a mechanical endurance going up to 20000 cycles. The Ue operational voltage is 230VAC or 240VAC. The Ui rated insulation voltage is 400VAC. The Uimp rated impulse withstand voltage is 4kV. The frequency is 50/60Hz. The product color is black (RAL9005). The dimensions are (W) 19mm x (H) 110mm x (D) 85mm. The weight is 186g. It has an IP20 degree of protection (as per IEC/EN 60529 standard) and becomes IP40 once in modular enclosure. The operating temperature is from -15°C to 60°C. The storage temperature is from -40°C to 85°C.

Product identifiers

SKU: QO120C10RCBO30F
EAN: 3606480569739
GTIN: 3606480569739
MPN: QO120C10RCBO30F

V+ Loyalty points: 130

Price: £ 359.03 Excl. VAT


Categories

Features

Frequency
50/60 Hz
Power loss
-
Voltage type
AC
Rated current
20 A
Rated voltage
240 V
Built-in depth
59 mm
Pollution degree
3
Rated fault current
0.03 A
Leakage current type
AC
Over voltage category
3
Current limiting class
3
Release characteristic
C
Surge current capacity
0.25 kA
Number of poles (total)
2
With interlocking device
FALSE
Degree of protection (IP)
IP20
Number of protected poles
1
Flush-mounted installation
FALSE
Rated insulation voltage Ui
400 V
Disconnection characteristic
Undelayed
Anti-nuisance tripping version
FALSE
Width in number of modular spacings
1
Ambient temperature during operating
Rated impulse withstand voltage Uimp
4 kV
Concurrently switching neutral conductor
FALSE
Connectable conductor cross section solid-core
Connectable conductor cross section multi-wired
Rated short-circuit breaking capacity according to EN 61009
-
Rated short-circuit breaking capacity according to IEC 60947-2
-
Rated short-circuit breaking capacity Icn according to EN 61009-1
10 kA