Miniature circuit-breaker, Acti9 iC40N, 1P+N, 10 A, B curve, 6000 A (IEC 60898-1), 10 kA (IEC 60947-2)

Miniature circuit-breaker, Acti9 iC40N, 1P+N, 10 A, B curve, 6000 A (IEC 60898-1), 10 kA (IEC 60947-2)

This Acti9 iC40N product is a low voltage miniature circuit breaker (MCB). It is a 1P+N circuit breaker with 1 protected pole and 10A In rated current and B tripping curve. The rated short circuit breaking capacity goes up to 10kA at 230VAC conforming to EN/IEC 60947-2 standard and 6000A at 230VAC conforming to EN/IEC 60898-1 standard. This product complies with both industrial standard EN/IEC 60898-1 and residential standard EN/IEC 60947-2. This miniature circuit breaker combines functions of circuit protection against short circuit and overload current, control and isolation. The installation and cabling are simplified with clip on function as well as ease of maintenance. It has an electrical endurance going up to 20000 cycles and a mechanical endurance going up to 20000 cycles. The Ue operational voltage is 230VAC. The Ui rated insulation voltage is 400VAC. The Uimp rated impulse withstand voltage is 4kV. The operating frequency is 50Hz or 60Hz. It can be mounted on DIN rail for modular installation. Its width is 2 pitches of 9mm. Pollution degree is 3. The product colour is white (RAL9003). The dimensions are (W) 18mm x (H) 85mm x (D) 74mm. The weight is 120g. According to IEC 60529 standard, the degree of protection is IP20 and IP40 in enclosure. The operating temperature is -25°C to 70°C. The storage temperature is -40°C to 85°C.

Product identifiers

SKU: A9P44610
EAN: 3606481324511
GTIN: 3606481324511
MPN: A9P44610

Voltimum+ Loyalty Programme Loyalty points: 6

Price: £ 52.22 Excl. VAT

Videos

How to video

Specifications

Frequency
Power loss 2.2 W
Voltage type AC
Rated current 10 A
Rated voltage 230 V
Built-in depth 44 mm
Explosion-proof no
Pollution degree 3
Current limiting class 3
Number of poles (total) 2
Number of protected poles 1
Rated insulation voltage Ui 400 V
Width in number of modular spacings 1
Rated impulse withstand voltage Uimp 4 kV
Connectable conductor cross section solid-core
Rated short-circuit breaking capacity Icn according to EN 60898 at 230 V 6 kA
Rated short-circuit breaking capacity Icu according to IEC 60947-2 at 230 V 10 kA