Residual Current Circuit Breaker with Overcurrent Protection

Residual Current Circuit Breaker with Overcurrent Protection

The DS201 series is a 1P+N RCBO in two-modules width for the protection of end user single-phase circuits against overload and short-circuit currents; protection against the effects of sinusoidal alternating and direct pulsating earth fault currents; protection against indirect contacts and additional protection against direct contacts. The APR type provides an optimal trade-off between safety and continuity of service, thanks to the resistance to unwanted trippings, offering good protection and isolation of resistive and inductive loads.

Product identifiers

SKU: 2CSR255480R2064
EAN: 8012542658115
GTIN: 8012542658115
MPN: DS201 C6 APR100

V+ Loyalty points:

92

Price: £ 0.00 Excl. VAT


Categories

Features

EFI00218
2.71653
EFI07337
-|-
EFI07343
0.0011|0.0248
EFI07515
-13|131
Frequency
50/60 Hz
Voltage type
AC
Rated current
6 A
Rated voltage
240 V
Built-in depth
69 mm
Pollution degree
2
Rated fault current
0.1 A
Leakage current type
A
Over voltage category
3
Current limiting class
3
Release characteristic
C
Surge current capacity
3 kA
Number of poles (total)
2
With interlocking device
no
Degree of protection (IP)
IP20
Number of protected poles
1
Flush-mounted installation
no
Rated insulation voltage Ui
500 V
Disconnection characteristic
Undelayed
Anti-nuisance tripping version
no
Width in number of modular spacings
2
Ambient temperature during operating
-25 - 55 °C
Rated impulse withstand voltage Uimp
4 kV
Concurrently switching neutral conductor
yes
Connectable conductor cross section solid-core
Connectable conductor cross section multi-wired
0.75 - 16 mm²
Rated short-circuit breaking capacity according to EN 61009
6 kA
Rated short-circuit breaking capacity according to IEC 60947-2
10 kA
Rated short-circuit breaking capacity Icn according to EN 61009-1
6 kA