Motor circuit breaker, TeSys GV2, 3P, 0.1-0.16 A, thermal magnetic, spring terminals

Motor circuit breaker, TeSys GV2, 3P, 0.1-0.16 A, thermal magnetic, spring terminals

TeSys GV motor circuit breaker, 3 poles (3P), 0.16A/690V, for 3-phase motor applications less than 0.06kW@400V. It provides a thermal-magnetic protection with a thermal setting range 0.1-0.16A, magnetic tripping at 9xIn, high breaking capacity Icu 100kA@400V. Connection by spring terminals. Start-stop control by push-button guaranteed for 100 000 cycles AC-3. Multi standards certified (IEC, UL, CSA, CCC, EAC, Marine, ATEX),

Product identifiers

SKU: GV2ME013
EAN: 3389110346343
GTIN: 3389110346343
MPN: GV2ME013

Voltimum+ Loyalty Programme Loyalty points: 9

Price range: £ 43.32 - £ 83.39 Excl. VAT

Videos

Promotional video

Specifications

Depth 78.5 mm
Width 45 mm
Height 101 mm
Power loss 2.5 W
Number of poles 3
Device construction Complete device in housing
Switch off technique Thermomagnetic
Phase failure sensitive yes
Type of control element Push button
Rated permanent current Iu 0.16 A
With integrated auxiliary switch no
Rated operation power at AC-3, 230 V 0.018 kW
With integrated under voltage release no
Adjustment range undelayed short-circuit release