Skip to content

Surge arrester with pluggable cartridge, Acti9 iPRD1 F25r, 3P+N, 25kA, type 1+2, with fuse, with remote monitoring

Surge arrester with pluggable cartridge, Acti9 iPRD1 F25r, 3P+N, 25kA, type 1+2, with fuse, with remote monitoring by Schneider Electric is listed by 1 electrical wholesaler on Voltimum UK, including City Electrical Factors, and currently in stock. Trade price £1,287.64 excl. VAT.

This Acti9 iPRD1 F25r surge arrester protects industrial and tertiary buildings installations against direct and indirect transient overvoltages. This is a 3P+N modular device with a 1+2 surge arrester class type with a surge adapted backup fuse. it offers a remote monitoring and also a front face local signalling with a green flag when the device is opeartional and with a red flag when the device needs to be changed. This prewired surge arrester allows quick replacement of withdrawable cartridges when they are damaged. It is compatible with TT and TN-S earthing system. It works on a Ue rated operational voltage of 240V AC under a frequency of 50Hz or 60 Hz. The Uc maximum continuous operating voltage is 275VAC in differential mode (L-N) and 305VAC in commun mode (N-PE). The In nominal discharge current is 25kA growing to a Imax maximum discharge current of 65kA with a L-N protection mode and 100kA growing to a Imax maximum discharge current of 150kA with a N-PE protection mode. The Iimp impulse current is 25kA in differential mode (N-PE) and 100kA in common mode (N-PE). The Up voltage protection level is 1.5kV in differential mode (L-N) and common mode (N-PE). It is clipped on the DIN rail. The dimensions are (W) 126mm x (H) 105mm x (D) 86mm. The weight is 1.187kg. The IP degree of protection is IP20. The operating temperature is -40°C to +85°C. This product complies with the EN 61643-11 standard with the 2011, 2012 and A11:2018 amendment.

Product identifiers

SKU: A9L1F625
EAN: 3606486808436
GTIN: 3606486808436
MPN: A9L1F625

Price: £ 1,287.64 Excl. VAT

Specifications

Test class Type 1 + 2
Max. PV-voltage -
Mounting method DIN rail (top hat rail) 35 mm
Number of poles 4
Construction size 7 modular spacing
Remote signalling yes
Nominal voltage AC 240 V
Nominal voltage DC -
Integrated backup fuse yes
System configuration IT no
System configuration TT yes
Voltage protection level 1.5 kV
System configuration TN-C no
Max. continuous voltage AC 275 V
System configuration other no
Voltage protection level L-N 1.5 kV
Voltage protection level N-PE 1.5 kV
Overcurrent protected voltage tapping -
Voltage switching spark gap technology no
Voltage protection level (DC+/DC- - PE) -
Max. conductor cross section solid (solid, stranded) 35 mm²
Max. overcurrent protection device, parallel connection (fuse) -

Documents

Declaration of Conformity (Sustainability)

A9L1F625 REACh Regulation

Open

Instruction sheet

Instruction sheet - Acti9 iPRD1 F25r Surge Protective Device (SPD) - Type 1 and Type 2

Open

Product data sheet

Open

Brochure

Acti9 & Resi9 new SPD - Leaflet

Open

Declaration of Conformity (Sustainability)

A9L1F625 EU RoHS Directive

Open

Declaration of conformity

UK Declaration of Conformity

Open

Environmental Disclosure

Acti9 iPRD1 F25r Surge Protective Device - Product Environmental Profile

Open

CAD

Open