Motor circuit breaker, TeSys GV2, 3P, 0.16-0.25 A, thermal magnetic, screw clamp terminals

Motor circuit breaker, TeSys GV2, 3P, 0.16-0.25 A, thermal magnetic, screw clamp terminals

TeSys GV motor circuit breaker, 3 poles (3P), 0.25A/690V, for 3-phase motor applications 0.06kW@400V. It provides a thermal-magnetic protection with a thermal setting range 0.16-0.25A, magnetic tripping at 9xIn, high breaking capacity Icu 100kA@400V. Connection by screw clamp terminals. Start-stop control by push-button guaranteed for 100 000 cycles AC-3. Multi standards certified (IEC, UL, CSA, CCC, EAC, Marine, ATEX),

Product identifiers

SKU: GV2ME02
EAN: 3389110342970
GTIN: 3389110342970
MPN: GV2ME02

Voltimum+ Loyalty Programme Loyalty points: 8

Price range: £ 39.67 - £ 63.67 Excl. VAT

Videos

Promotional video

Specifications

Depth 78.2 mm
Width 45 mm
Height 89 mm
Power loss 2.5 W
Number of poles 3
Device construction Complete device in housing
Switch off technique Thermomagnetic
Phase failure sensitive yes
Type of control element Push button
Rated permanent current Iu 0.25 A
With integrated auxiliary switch no
Rated operation power at AC-3, 230 V 0.037 kW
With integrated under voltage release no
Adjustment range undelayed short-circuit release