Type
|
Accessory |
|
Series
|
RMQ-16 |
|
Environmental rating
|
IP65 |
|
Size
|
16.2 mm |
|
10.10 Temperature rise
|
The panel builder is responsible for the temperature rise calculation. Eaton will provide heat dissipation data for the devices. |
|
10.11 Short-circuit rating
|
Is the panel builder's responsibility. The specifications for the switchgear must be observed. |
|
10.12 Electromagnetic compatibility
|
Is the panel builder's responsibility. The specifications for the switchgear must be observed. |
|
10.13 Mechanical function
|
The device meets the requirements, provided the information in the instruction leaflet (IL) is observed. |
|
10.2.2 Corrosion resistance
|
Meets the product standard's requirements. |
|
10.2.3.1 Verification of thermal stability of enclosures
|
Meets the product standard's requirements. |
|
10.2.3.2 Verification of resistance of insulating materials to normal heat
|
Meets the product standard's requirements. |
|
10.2.3.3 Resist. of insul. mat. to abnormal heat/fire by internal elect. effects
|
Meets the product standard's requirements. |
|
10.2.4 Resistance to ultra-violet (UV) radiation
|
Meets the product standard's requirements. |
|
10.2.5 Lifting
|
Does not apply, since the entire switchgear needs to be evaluated. |
|
10.2.6 Mechanical impact
|
Does not apply, since the entire switchgear needs to be evaluated. |
|
10.2.7 Inscriptions
|
Meets the product standard's requirements. |
|
10.3 Degree of protection of assemblies
|
Does not apply, since the entire switchgear needs to be evaluated. |
|
10.4 Clearances and creepage distances
|
Meets the product standard's requirements. |
|
10.5 Protection against electric shock
|
Does not apply, since the entire switchgear needs to be evaluated. |
|
10.6 Incorporation of switching devices and components
|
Does not apply, since the entire switchgear needs to be evaluated. |
|
10.7 Internal electrical circuits and connections
|
Is the panel builder's responsibility. |
|
10.8 Connections for external conductors
|
Is the panel builder's responsibility. |
|
10.9.2 Power-frequency electric strength
|
Is the panel builder's responsibility. |
|
10.9.3 Impulse withstand voltage
|
Is the panel builder's responsibility. |
|
10.9.4 Testing of enclosures made of insulating material
|
Is the panel builder's responsibility. |
|
Electric connection type
|
Screw connection |
|
Operating frequency
|
3600 Operations/h |
|
Pollution degree
|
3 |
|
Climatic proofing
|
Damp heat, constant, to IEC 60068-2-78 Damp heat, cyclic, to IEC 60068-2-30 |
|
Actuating force - max
|
3 N |
|
Ambient operating temperature - max
|
60 °C |
|
Ambient operating temperature - min
|
-25 °C |
|
Ambient operating temperature (enclosed) - max
|
40 °C |
|
Ambient operating temperature (enclosed) - min
|
-25 °C |
|
Equipment heat dissipation, current-dependent Pvid
|
0 W |
|
Heat dissipation capacity Pdiss
|
0 W |
|
Heat dissipation per pole, current-dependent Pvid
|
0.1 W |
|
Number of contacts (change-over contacts)
|
0 |
|
Number of contacts (normally closed contacts)
|
0 |
|
Number of contacts (normally open contacts)
|
1 |
|
Number of switches (fault signal)
|
0 |
|
Connection to SmartWire-DT
|
No |
|
Rated impulse withstand voltage (Uimp)
|
4000 V AC |
|
Terminal capacity
|
0.5 - 1.0 mm² |
|
Mounting position
|
As required |
|
Terminal size
|
2.8 x 0.8 mm to DIN 46247 and IEC 60760, Fast-on connectors 2.8 x 0.8 mm to DIN 46244, Blade terminal |
|
Rated conditional short-circuit current (Iq)
|
1 kA |
|
Connection type
|
Blade terminal |
|
Mounting method
|
Front fastening |
|
Overvoltage category
|
III |
|
Control circuit reliability
|
1 failure per 10,000,000 switching operations (Statistically determined, at 24 V DC/5 mA) 1 failure per 5,000,000 switching operations (statistically determined, at 5 V DC/1 mA) |
|
Degree of protection
|
IP20, with Insulated ferrule ISH2,8 |
|
Model
|
Top mounting |
|
Lamp holder
|
None |
|
Rated operational current (Ie)
|
4 A at AC-15, 110 V 4 A at AC-15, 48 V |
|
Lifespan, mechanical
|
100,000,000 Operations |
|
Short-circuit protection
|
FAZ-B6/1, Fuseless |
|
Static heat dissipation, non-current-dependent Pvs
|
0 W |
|
Product category
|
Accessories |
|
Short-circuit protection rating
|
Max. 10 A gG/gL, Fuse, Contacts |
|
Rated insulation voltage (Ui)
|
250 V |
|
Rated operational current (Ie) at AC-15, 220 V, 230 V, 240 V
|
6 A |
|
Rated operational current (Ie) at AC-15, 24 V
|
4 A |
|
Rated operational current (Ie) at DC-13, 110 V
|
0.5 A |
|
Rated operational current (Ie) at DC-13, 220 V, 230 V
|
0.2 A |
|
Rated operational current (Ie) at DC-13, 24 V
|
1.5 A |
|
Rated operational current (Ie) at DC-13, 42 V
|
1 A |
|
Rated operational current (Ie) at DC-13, 60 V
|
0.8 A |
|
Rated operational current for specified heat dissipation (In)
|
4 A |
|
Rated operational voltage (Ue) at AC - max
|
250 V |
|
Shock resistance
|
40 g, Mechanical, According to IEC/EN 60068-2-27, Sinusoidal shock 11 ms Mechanical, According to IEC/EN 60068-2-27 |