Used with
|
Miniature circuit breaker EM |
|
Amperage Rating
|
40 A |
|
Features
|
Additional equipment possible |
|
Pollution degree
|
2 |
|
Degree of protection
|
IP20 |
|
Equipment heat dissipation, current-dependent
|
4.4 W |
|
Rated impulse withstand voltage (Uimp)
|
4 kV |
|
Tripping characteristic
|
D |
|
Ambient operating temperature - max
|
55 °C |
|
Ambient operating temperature - min
|
-25 °C |
|
Built-in depth
|
75 mm |
|
Connectable conductor cross section (multi-wired) - max
|
50 mm² |
|
Connectable conductor cross section (multi-wired) - min
|
2.5 mm² |
|
Connectable conductor cross section (solid-core) - max
|
50 mm² |
|
Connectable conductor cross section (solid-core) - min
|
2.5 mm² |
|
Current limiting class
|
3 |
|
Frequency rating - max
|
60 Hz |
|
Frequency rating - min
|
50 Hz |
|
Heat dissipation capacity
|
0 W |
|
Width in number of modular spacings
|
4.5 |
|
Voltage type
|
AC |
|
Overvoltage category
|
III |
|
Number of poles
|
Three-pole |
|
Release characteristic
|
D |
|
Type
|
EMMiniature circuit breaker |
|
Special features
|
Ambient temperature hint: a 1 °C increase results in a 0.35% linear reduction of current carrying capacity |
|
Application
|
Switchgear for residential and commercial applications |
|
Number of poles (protected)
|
3 |
|
Number of poles (total)
|
3 |
|
Rated insulation voltage (Ui)
|
440 V |
|
Rated operational current for specified heat dissipation (In)
|
40 A |
|
Rated operational voltage (Ue) - max
|
400 V |
|
Rated short-circuit breaking capacity (IEC 60947-2)- Icu at 230 V
|
25 kA |
|
Rated short-circuit breaking capacity (IEC 60947-2)- Icu at 400 V
|
25 kA |
|
Rated switching capacity (IEC/EN 60947-2)
|
25 kA |
|
Static heat dissipation, non-current-dependent
|
0 W |