TeSys LRD thermal overload relay, 120A/1000V, thermal setting range 95-120A, tripping class 10A, for protection of 3-phase motors 55kW@400V. Differential device with phase failure and load unbalance detection. It provides a thermal adjustement dial, a manual-automatic reset selector acting also as reset button, a trip test button for simulation of a tripping, a stop button, a flag indicator and 2 auxiliary contacts 1NO+1NC for fault signalling. Settings are protected by a transparent cover lockable by sealing. Connection by screw clamp terminals, it connects directly to the bottom terminals of 3-pole contactors LC1D115-D150. Mounting on DIN rail or screw fixing, separated from the contactor, with use of a terminal block LA7D3064 (to be ordered separately). Multi standards certified (IEC, UL, CSA, CCC, EAC, ATEX, Marine),
Product identifiers
SKU: LRD4367
EAN: 3389110523348
GTIN: 3389110523348
MPN: LRD4367
Loyalty points:
39
Price range: £ 282.78 - £ 292.68 Excl. VAT
ETIM Group
Videos
Promotional video
Specifications
| Release class | CLASS 10 A |
| Mounting method | Direct attachment |
| Reset function input | no |
| Adjustable current range | |
| Reset function automatic | yes |
| Reset function push-button | yes |
| Max. rated operation voltage Ue | 1000 V |
| Type of electrical connection of main circuit | Screw connection |