IPRD8 modular surge arrester - 1P + N - 350V

IPRD8 modular surge arrester - 1P + N - 350V

This Acti9 iPRD8 surge arrester protects 1P+N installations. It allows quick replacement of damaged cartridges. Modular design (cartridge type) DIN rail mounted This surge arrester is required when the loads to be protected are at a distance of more than 10 m from the incoming surge arrester. The Uc maximum continuous operating voltage in common mode is 260VAC between neutral and earth, and 350VAC between phase and earth. The Uc maximum continuous operating voltage in diiferential mode (between phase and neutral) is 350VAC. The Up Voltage protection level in common mode is 1.4kV between neutral and earth in type 2, and 1.1kV between neutral and earth in type 3. The Up Voltage protection level in differential mode (between phase and neutral) is 1kV in type 2, and 1.1kV in type 3. The Ue rated operational voltage is 230VAC +/- 10%. The product colour is white (RAL9003).The dimensions are (W) 36mm x (H) 85mm x (D) 69mm. The weight is 0.211kg. The degree of protection is IP20 and IP40 in modular enclosure. The operating temperature is -25°C to 60°C. The storage temperature is -40°C to 85°C. This product is compliant with EN 61643-11 and IEC 61643-11 standard.

Product identifiers

SKU: A9L08500
EAN: 3606480506574
GTIN: 3606480506574
MPN: A9L08500

V+ Loyalty points: 106

Price range: £ 206.86 - £ 268.74 Excl. VAT


Categories

Features

Category type 2
TRUE
Max. PV-voltage
-
Mounting method
DIN rail (top hat rail) 35 mm
Construction size
2 modular spacing
Nominal voltage AC
230 V
Nominal voltage DC
-
Leakage-current free
FALSE
Integrated backup fuse
FALSE
System configuration DC
FALSE
System configuration IT
FALSE
System configuration TN
FALSE
System configuration TT
TRUE
Signalling at the device
Optical
Voltage protection level
1 kV
Degree of protection (IP)
IP20
System configuration TN-C
FALSE
System configuration TN-S
TRUE
Max. continuous voltage AC
350 V
Max. continuous voltage DC
-
System configuration other
FALSE
System configuration TN-C-S
FALSE
Voltage protection level L-N
1.1 kV
Voltage protection level N-PE
1.4 kV
With remote signalling contact
FALSE
Integrated short-circuit protection
FALSE
Max. discharge surge current (8/20)
8 kA
Nominal discharge surge current (8/20)
2.5 kA
Number of conductors (without earthing)
1
Short-circuit breaking capacity (Isccr)
50 kA
Max. conductor cross section flexible (fine-strand)
35 mm²
Max. conductor cross section solid (solid, stranded)
35 mm²
Integrated short-circuit protection selective to fuse gG
-
Max. overcurrent protection device, series connection (fuse)
80 A
Max. overcurrent protection device, parallel connection (fuse)
25 A