IPRD8 modular surge arrester - 1P + N - 350V
This Acti9 iPRD8 surge arrester protects 1P+N installations. It allows quick replacement of damaged cartridges. Modular design (cartridge type) DIN rail mounted This surge arrester is required when the loads to be protected are at a distance of more than 10 m from the incoming surge arrester. The Uc maximum continuous operating voltage in common mode is 260VAC between neutral and earth, and 350VAC between phase and earth. The Uc maximum continuous operating voltage in diiferential mode (between phase and neutral) is 350VAC. The Up Voltage protection level in common mode is 1.4kV between neutral and earth in type 2, and 1.1kV between neutral and earth in type 3. The Up Voltage protection level in differential mode (between phase and neutral) is 1kV in type 2, and 1.1kV in type 3. The Ue rated operational voltage is 230VAC +/- 10%. The product colour is white (RAL9003).The dimensions are (W) 36mm x (H) 85mm x (D) 69mm. The weight is 0.211kg. The degree of protection is IP20 and IP40 in modular enclosure. The operating temperature is -25°C to 60°C. The storage temperature is -40°C to 85°C. This product is compliant with EN 61643-11 and IEC 61643-11 standard.
Product identifiers
SKU: A9L08500
EAN: 3606480506574
GTIN: 3606480506574
MPN: A9L08500
Loyalty points: 106
Price range: £ 206.86 - £ 268.74 Excl. VAT
Categories
Features
Category type 2
|
TRUE
|
Max. PV-voltage
|
-
|
Mounting method
|
DIN rail (top hat rail) 35 mm
|
Construction size
|
2 modular spacing
|
Nominal voltage AC
|
230 V
|
Nominal voltage DC
|
-
|
Leakage-current free
|
FALSE
|
Integrated backup fuse
|
FALSE
|
System configuration DC
|
FALSE
|
System configuration IT
|
FALSE
|
System configuration TN
|
FALSE
|
System configuration TT
|
TRUE
|
Signalling at the device
|
Optical
|
Voltage protection level
|
1 kV
|
Degree of protection (IP)
|
IP20
|
System configuration TN-C
|
FALSE
|
System configuration TN-S
|
TRUE
|
Max. continuous voltage AC
|
350 V
|
Max. continuous voltage DC
|
-
|
System configuration other
|
FALSE
|
System configuration TN-C-S
|
FALSE
|
Voltage protection level L-N
|
1.1 kV
|
Voltage protection level N-PE
|
1.4 kV
|
With remote signalling contact
|
FALSE
|
Integrated short-circuit protection
|
FALSE
|
Max. discharge surge current (8/20)
|
8 kA
|
Nominal discharge surge current (8/20)
|
2.5 kA
|
Number of conductors (without earthing)
|
1
|
Short-circuit breaking capacity (Isccr)
|
50 kA
|
Max. conductor cross section flexible (fine-strand)
|
35 mm²
|
Max. conductor cross section solid (solid, stranded)
|
35 mm²
|
Integrated short-circuit protection selective to fuse gG
|
-
|
Max. overcurrent protection device, series connection (fuse)
|
80 A
|
Max. overcurrent protection device, parallel connection (fuse)
|
25 A
|