What do I need to consider regarding the single or double bypass of transfer switches?

Published: 19 November 2020 Category: Q&A

Our expert answers a question from a Voltimum user regarding fire standards in relation to transfer switches.

What do I need to consider regarding the single or double bypass of transfer switches?

We recently ran a live webinar covering fire standards in relation to transfer switches which can be viewed here: 

Below you will find one of the questions from the Q&A at the end.

Question:

Do you need to have a single or double bypass?

Answer

Under the fire standards you only need a single, but be aware for critical loads - if you take the ATS out of service for maintenance when you're in source one, if you lose source one and want to transfer to source two, you can only do that with a double bypass. However most only require a single bypass.

- Michael Lonsdale - UK Sales Manager, Socomec