Andy Mothersele asks this question, which concerns the electrical supply to a newly installed whirlpool bath. It has been answered by SELECT (Theme – Regulations & Legislation):
Question: Is it a requirement under the 17th Edition Wiring Regulations to fit a totally new separate supply for a new whirlpool installation in a bathroom?
Alternatively, can an RCD-protected fused spur off the ring main suffice?
Answer: An RCD-protected fused connection unit (located outwith the bathroom or shower room) supplying such equipment will meet the requirements.
To see many more Q & A in Voltimum UK's Experts Area, please click on the link:
www.voltimum.co.uk/consult.php?universe=consult.index.questions