Published: 3 January 2014 Category: Q&A

David asks this question, which concerns the supply cable to a mag lock control panel controlled via volt free contacts on a fire alarm panel. It has been answered by SELECT (Theme – Fire, Safety and Security):

Q & A of the Day – Must I wire this fire control panel system in fire rated cable?

This Q & A is one of thousands posted in our Technical Expertise area, and answered on a daily basis by our Voltimum Experts.

Question: Can anyone advise me as to whether the supply cable to a mag lock control panel that is controlled via volt free contacts on a fire alarm panel has to be wired in fire rated cable?

At present, it is wired from the fire alarm spur in FP200 cable, and I need to put them on a separate supply. As they are wired in FP200, I do not know whether this can be wired in PVC twin and earth cable.

Answer: The mains supply to a fire alarm panel requires to be wired using fire resisting cable.

The mains supply to an associated door release control panel, however, does not require to be wired using fire resisting cable.

To see many more Q & A in Voltimum UK's Experts Area, please click on the link. Experts from leading organisations provide online answers to your technical questions on a broad range of subjects. Our searchable database of existing Q & As now contains over 3,500 entries; you can browse through them here.