Our Voltimum Experts answer your questions on a daily basis in our Technical Expertise area. This Question of the Day, concerning the earthing of liquid propane gas (LPG) storage tanks at a hotel, is answered by the NICEIC:
Can you advise which regulations would provide guidance on the requirements?
Answer: Under current BS7671:2008 (17th Edition) there is no requirement to bond the LPG tanks outside.
Where the gas pipe comes into the property, the same requirements as your gas and water main coming into the property exists. Please refer to Regulation 411.3.1.2.
For the location of the bonding, refer to Regulation 544.1.2.