John Dalgetty asks about possible RCD protection for the SWA cable at a consumer unit (CU) supplying a septic tank pump. It is answered by the ECA (Theme – Fire, Safety & Security):

Q & A of the Day – Should I install an RCD to protect SWA cable at the house CU?

This Q & A is one of thousands posted in our Technical Expertise area, and answered on a daily basis by our Voltimum Experts.

Question: I have currently installed an SWA cable to supply an exterior sump pump for a septic tank system for a domestic dwelling.

The exterior pump panel has been pre-wired with 30mA RCD protection as factory specification.

Is there a requirement to RCD protect the SWA cable at the house consumer unit?

Answer: An RCD would not be required, provided that the Zs is sufficiently low to meet the disconnection time.