Peter Monsen asks whether he must prepare a second EICR – one for the house and another for the garage. His question has been answered by the NICEIC (Theme – Regulations & Legislation):
Question: I'm in the middle of completing a re-wire, and the client requires a garage distribution board feeding one 20A radial circuit for socket outlets and one 6A lighting circuit.
My question is - when completing a domestic test certificate (EICR), do I have to write another for the garage distribution board that is being supplied from a 40A MCB with an 80A RCD mains switch from the main consumer unit of the house?
Answer: An EICR can be provided for the complete installation. However, a separate test results page must be completed for each distribution board, and it must be clearly marked to indicate that the garage board is fed from a sub-main from the house consumer unit.
If you refer to the NICEIC's Inspection, Testing and Certification handbook, it gives guidance on this issue.
Please read the attached document (page 148) for your reference (PDF - 846kB file size) - please click on the link near the bottom of this web page.