Q & A of the Day – Must I ask the supply company to change meter tails?

Published: 21 May 2009 Category: Q&A

Our Voltimum Experts answer your questions on a daily basis in our Technical Expertise area. This one, about meter tails and seal protection, is answered by SELECT:

Q & A of the Day – Must I ask the supply company to change meter tails?
Question: When changing a fuseboard, I understand that the tails must be increased in size. In terms of the earthing (also including the main bonding), the main earthing conductor will be increased to 16mm as the tails will need to be 25mm. This will be no problem, as it is not protected with a seal!

The question is - do I need to inform the supply company, and ask it to come and change the tails? The reason I ask this is because I'm not legally allowed to cut the seals and see no reason to upgrade the size of the tails from the meter to the consumer unit if the tails from the main fuse to meter are going to remain 16mm.

Answer: As you indicate, meter tails will normally be increased to 25mm2 and the main earthing conductor to 16mm2. To be able to do this, some contact with the supply company or distributor will be necessary to break seals (if in position), and/or to install a switch disconnector.