Q & A of the Day – Is it OK to parallel three smaller sub-main cables, rather than using two large cables?

Published: 5 May 2015 Category: Q&A

Phil has asked this question about whether three four-core cables in parallel can be used in place of two larger cable to help solve handling issues. It has been answered by the ECA (Theme - Distribution Equipment including Cable Management):

Q & A of the Day – Is it OK to parallel three smaller sub-main cables, rather than using two large cables?

This Q & A is one of thousands posted in our Technical Expertise area, and answered on a daily basis by our Voltimum Experts.

Question: We have a 400kW electrical machine to feed at 0.8 power factor TP/N to a distance of 127m. Is it possible to parallel up three smaller sub-main feeder cables, rather than using two larger cables? 

The reason I’d like to do this is because of the difficulty man-handling the larger cables on-site.

And if this is OK, what are the formulas with regard to volt drop in three parallel cables?

Answer: Yes, subject to the cables all being of the same size and installed in the same route, this arrangement should be fine. 

The volt drop calculation result would then need to be divided by three. 

To see many more Q & A in Voltimum UK's Experts Area, please click on the link. Experts from leading organisations provide online answers to your technical questions on a broad range of subjects. Our searchable database of existing Q & As now contains over 3,500 entries; you can browse through them here.