Our Voltimum Experts answer your questions on a daily basis in our Technical Expertise area. This Question of the Day, about partition walls and bonding of studs, is answered by SELECT:

Answer: No. But where metal stud partition walls are installed, and the installation is not under the supervision of a skilled or instructed person, then any cables passing through should be suitably protected by either earthed metallic protection, or a 30mA RCD.
Where the likes of thermoplastic cables pass though the metal stud partition wall, suitable bushing - such as grommets - should be used to prevent possible mechanical damage.
Photo by XPR Systems.
For further details see 522.6.8.