Jerry asks this question, which concerns low voltage (LV) power cable DC voltage ratings. It has been answered by BASEC (Theme – Cable, Wiring and Wiring Accessories):

This Q & A is one of thousands posted in our Technical Expertise area, and answered on a daily basis by our Voltimum Experts.
Question: Standard LV power cable is rated at 0.6/1kV. Is the DC voltage rating of these cables the same as the definition in BS 7671, which states that the LV DC power is 1,500 VDC?
Answer: The reference to DC voltage rating in BS 7671 may relate to the DC voltage limit defined in the Low Voltage Directive. For AC, this is 1000V, and for DC it is 1500V.
LV cable standards generally provide AC voltage ratings (such as 600/1000V) but many also include informative DC ratings. For example, in BS 6724 (600/1000V AC LSHF armoured power cables), indicative DC ratings are offered in Annex A, which are 1000V DC for single core cables and 1500V DC for two-core cables (between conductors).
The cable manufacturer should be consulted if there is any uncertainty.
To see many more Q & A in Voltimum UK's Experts Area, please click on the link. Experts from leading organisations provide online answers to your technical questions on a broad range of subjects. Our searchable database of existing Q & As now contains over 3,500 entries; you can browse through them here.