Q & A of the Day – Can we use this data centre loading as the electrical load?

Published: 27 August 2009 Category: Q&A

Our Voltimum Experts answer your questions on a daily basis in our Technical Expertise area. This one, concerning a data centre, its loading and the building’s electrical load, is answered by SELECT:

Q & A of the Day – Can we use this data centre loading as the electrical load?
Question: A data centre is specified with 200,000 BTU heat loading, which is equivalent to 50kW (based on btu per hr/ 3.41= watt).

The question is - can we use this 50kW as the electrical load, so as to calculate the electrical loading of the facility?

Answer: The 200,000 Btu's specified is for the heating/ACU loading of the building and does not relate to its electrical loading. The electrical loading will be based on the rating of all of the electrical equipment in use, bearing in mind that diversity will have to be taken into account.