Our Voltimum Experts answer your questions on a daily basis in our Technical Expertise area. This one, concerning RCD test values on a TT system in a house, is answered by SELECT:

I have two questions:
1) Can I record the max permitted Zs for each circuit as 1667 ohms 50/30mA on the test sheet, as the max values for MCBs in the Regulations is for TN Systems, not TT?
2) When testing the 30mA RCDs, the rated test value is 32ms and the five times test value is 9ms. Seeing that the max disconnection time is 20ms for a TT system, are the values OK, even though only the five times test meets the requirement?
Answer: For a new installation carried out to BS 7671:2008, in a domestic or similar premises with a TT earthing system, you would normally provide a dual board with two 30mA RCDs or RCBOs for each of the circuits.
The recorded Zs values would be based on the protective device in place, i.e. the MCB.
Appendix 3 of BS 7671:2008 gives the requirements for testing RCDs.
To see many more Q & A in Voltimum UK's Experts Area, please click on the link:
www.voltimum.co.uk/consult.php?universe=consult.index.questions