57 - Minimum cross-sections of electrical conductors according to IEC 60364-5-52

Published: 5 August 2011 Category: News

This section is devoted to assessing the extent depending on the type of cable laying and other parameters.

Type of pipelineUsing the circuitMaterialConductor cross-section
[mm2]
Notes
Cables fixed pipelinePower and lighting circuitsCopper1,5-
Cables fixed pipelinePower and lighting circuitsAluminium2,5It is recommended that the means used to connect the ends of the Aluminium conductors are tested and approved for this specific use
Cables fixed pipelineControl and signaling circuitsCopper0,5Signal and control circuits for electronic equipment is allowed a minimum diameter of 0.1 mm2
Fixed pipeline bare conductorsPower and lighting circuitsCopper10-
Fixed pipeline bare conductorsPower and lighting circuitsAluminium16-
Fixed pipeline bare conductorsControl and signaling circuitsCopper4-
Flexible connections with cables (with and without sheath)For a specific applianceCopperAs specified in the corresponding IEC
Flexible connections with cables (with and without sheath) For any other appliance Copper0,75 For multicore flexible cables, which contain seven or more, the allowable section of 0.1 mm2
Flexible connections with cables (with and without sheath)Low voltage circuits for special applicationsCopper0,75-