SELECT

Which is the best calculation for checking the readings on R1 RN end to end on ring main?

Published: 13 January 2023 Category: Q&A

ASK AN EXPERT! Our expert from SELECT answers the question from a Voltimum user.

Which is the best calculation for checking the readings on R1 RN end to end on ring main?

QUESTION:

Which is the best calculation to use for checking the readings on R1 RN end to end on ring main so I know it’s not measuring high?

ANSWER:

The value will be approximately one-quarter of the resistance of the line and neutral conductor loop resistances, i.e. (R1+Rn)/4

Bob Cairney, Stuart McKelvie, Keith Hagan, Neil Sim and Mark McLaughlin

Experts on all aspects of Electrical Installation Scottish Building Standards

SELECT

Contact SELECT here