Requirements for failed lighting circuits on an EICR.
Question:
Is there a requirement to protect a circuit with an RCD wired in swa cables?
Some background: We have a job to replace some bollard lighting that has failed an EICR inspection as some of them are broken. The bollards are on the communal grounds of a housing development, and the lighting circuit is a mixture of bollards and lamp-posts.
Answer:
Gary Parker
Not necessarily. There is no requirement in BS 7671 to RCD-protect external circuits or cables underground unless there are other elements in play such as the installation is part of a TT earthing system or there are high earth fault loop impedance values.