400TR - Interface C - Test rods

400TR - Interface C - Test rods

EUROMOLD test rods

Application

  • The test rod can be used for:
          - cable fault location
          - cable testing
          - phasing checks, etc.
  • Connections may be made with a cable lug, a 4 mm plug or spring clips.

Technical characteristics

  • The 400TR test rod can be used with 400TE, 430TB, 400TB and 440TB connectors.

Product identifiers

SKU: 5451458
MPN: 5451458

Price: £ 0.00 Excl. VAT

Specifications

Standards

Product CENELEC EN 50180
Test CENELEC HD 629.1

Usage characteristics

Interface C (630 - 1250 A)

Electrical characteristics

Rated Voltage Uo/U (Um) 12 / 20 (24) kV
Maximal partial discharge at 2Uo - pC
Dielectric withstand voltage, 50Hz 1mn 36 kV
Impulse voltage 95 kV

Dimensional characteristics

Conductor cross-section, range 0 ... 0 mm²