Thermal magnetic circuit breaker, TeSys GB2, 1P, 0.5 A, Icu 50 kA@240 V, low magnetic tripping level

Thermal magnetic circuit breaker, TeSys GB2, 1P, 0.5 A, Icu 50 kA@240 V, low magnetic tripping level

TeSys GB circuit breaker, 1 pole (1P), 0.5A/250V, low tripping threshold, for the protection of industrial equipment control circuits. It provides thermal magnetic protection with a magnetic tripping level at 3.3A (6 In) and breaking capacity Icu 50kA@240V. It can also be used for protection of DC loads up to 0.5A/48V DC-13 with a breaking capacity Icu 1.5kA@24V. Compact device (15mm wide), mounting on 35mm DIN-rail, control by toggle lever (start-stop guaranteed for 8000 cycles). Sold in lots of 6 units. It conforms to IEC 60947-1 and IEC 60947-2.

Product identifiers

SKU: GB2CS05
EAN: 3389110431612
GTIN: 3389110431612
MPN: GB2CS05

Voltimum+ Loyalty Programme Loyalty points: 4

Price: £ 40.45 Excl. VAT

Specifications

Frequency
Power loss -
Voltage type AC
Rated current 0.5 A
Rated voltage 250 V
Built-in depth 75 mm
Explosion-proof no
Pollution degree 2
Current limiting class 3
Number of poles (total) 1
Number of protected poles 1
Rated insulation voltage Ui 250 V
Width in number of modular spacings 2
Rated impulse withstand voltage Uimp 4 kV
Connectable conductor cross section solid-core
Rated short-circuit breaking capacity Icn according to EN 60898 at 230 V -
Rated short-circuit breaking capacity Icu according to IEC 60947-2 at 230 V 50 kA