Q & A of the Day – Can 25mm tails be ducted underground from fuseboard to meter box?

Published: 23 October 2012 Category: Q&A

Steven Wakefield asks whether it is acceptable to run 25mm meter tails in ducting under the ground from the fuse board to outside the meter box. His question has been answered by the NICEIC (Theme – Distribution Equipment):

Q & A of the Day – Can 25mm tails be ducted underground from fuseboard to meter box?
This Q & A is one of thousands posted in our Technical Expertise area, and answered on a daily basis by our Voltimum Experts.

Question: Is it OK to run 25mm tails in ducting under the ground from the fuse board to outside the meter box? Note that the length of the tails is 7/8 meters and they connect into a KMF switch in the meter box.

I can't really put the switch anywhere else....

Answer: If the meter tails are run above three metres long, and are additionally mechanically protected, then an isolator should be installed at the origin of those tails to ensure adequate safety, and to be able to work on them.