Our Voltimum Experts answer your questions on a daily basis in our Technical Expertise area. This Question of the Day, concerning the correct specification for heat-resisting cable, is answered by BASEC:



Heat resistant cable - what spec to choose?
Heat resistant cable - what spec to choose?
pixel
Question: I have a customer looking for 1 square mm heat resisting cable to IEC 60245-7 (1994), with a temperature range of up to 110oC. Is this a correct specification, ie: the 110oC?

Answer: This specification sounds sensible and the temperature rating is correct for this type of cable.

The standard referred to is:

IEC 60245-7 Rubber Insulated Cables - Rated Voltages up to and Including 450/750 V - Part 7: Heat Resistant Ethylene-Vinyl Acetate Rubber Insulated Cables. Published 1994, with Amendment 1 published 1997.

Similar small size cables (for 1mm sq) are available to European standards, and these would be harmonised types H05G-U (solid core), H05G-K (flexible). The relevant British Standards for these is BS 6007:2006, Electric cables. Single core unsheathed heat-resisting cables for voltages up to and including 450/750 V, for internal wiring.

These BS 6007 cables are also EVA insulated and rated at 110oC.

To see many more Q & A in Voltimum UK's Experts Area, please click on the link:

http://www.voltimum.co.uk/consult.php?universe=consult.index.questions

If you like this article and want to share it with friends, please use the social links below:

 Back

 Related contacts
The British Approvals Service for Cables (BASEC)
23 Presley Way, Crownhill,
Milton Keynes MK8 0ES
Tel: 01908 267300
Fax: 01908 267255
Email: mail@basec.org.uk
Web: www.basec.org.uk
blue arrow pointing right   BASEC

 For latest electrical industry news, register for Voltimum's free newsletter.
Enter your email address here:
OK

Source: BASEC & James Hunt

Related information

Related contacts

More News...

Q & A of the Day – What cable for exterior uplighters?
Q & A of the Day - What is the lifespan of twin and earth cable?
Q & A of the Day - meter tail sizes
Q & A of the Day - SY CC cable used outside
A Day in the Life of... BASEC's lead cable assessor
BASEC suggests caution on cabling for homes
BASEC delivers warning on Home Condition Report
Assess fire risk, warns BASEC