Q & A of the Day - Main equipotential bonding – what type of joint?

BookmarkThis 31.03.2008
SELECT
 

Our Voltimum Experts answer your questions on a daily basis in our Technical Expertise area. This Question of the Day, concerning main equipotential bonding and the type of joint to be used, is answered by SELECT:

Use a crimp joint if conductor is broken.
Use a crimp joint if conductor is broken.
pixel
Question: Is it acceptable to mechanically join the 10mm main equipotential bonding cable running from the consumer unit to the rising main, then onto the gas main? If yes, is there any restriction on the type of mechanical joint used?

We regularly come across bonding which is 'broken' at the mid-point and would clearly prefer to join rather than replace, if such an approach were to be acceptable under the Regulations.

Answer: Main bonding conductors may be looped from one extraneous-conductive-part to another but the conductor must be continuous. If the conductor is broken at such a point, the two conductors should be crimped together. They should be connected to pipes, etc, using an earth clamp to BS 951.

To see many more Q & A in Voltimum UK's Experts Area, please click on the link:

http://www.voltimum.co.uk/consult.php?universe=consult.index.questions

 Back

 Related contacts
SELECT
The Walled Garden, Bush Estate,
Midlothian, Scotland EH26 0SB
Tel: 0131 445 5577
Fax: 0131 445 5548
Email: admin@select.org.uk
Web: www.select.org.uk
blue arrow pointing right   SELECT

 For latest electrical industry news, register for Voltimum's free newsletter.
Enter your email address here:
OK

Source: SELECT & James Hunt

Related information

Related contacts

More News...

Q & A of the Day – Can I run a separate supply to this machine socket-outlet?
Q & A of the Day – Must I buy new software for BS7671:2008 First Amendment?
Q & A of the Day – Should I use female bushes when mounting conduit box to metal trunking?
Q & A of the Day – Should I install an RCD to protect SWA cable at the house CU?
Q & A of the Day – What is the difference between City & Guilds 2391-10 and 2392 courses?
Q & A of the Day – Is there a problem with this client’s inspection report request?
Q & A of the Day – What is the right way to fit an SPD?
Q & A of the Day - Sockets by the seaside – what IP rating?
Q & A of the Day - What is required in terms of proximity of water/power supply cables?