Q & A of the Day - Earth fault loop impedance testing

N.A.P.I.T
 
Our Voltimum Experts answer your questions on a daily basis in our Technical Expertise area. This one, about earth fault loop impedance testing, is answered by NAPIT:

Meggar's LT7 digital loop tester.
Meggar's LT7 digital loop tester.
pixel
Question: Could you please tell me if whether could carry out earth loop impedance testing (ie: Ze and Zs) if there is no equipotential earth bonding connected. When using a Meggar LT7 digital loop tester, it appears that the instrument goes through a checking process before the test is displayed.

Answer: I'll discuss the checking process in a moment. First, when measuring Ze, the means of earthing must be disconnected from the installation earthed equipotential bonding for the duration of the test to remove parallel paths.

When measuring Zs, neither the means of earthing, nor the bonding conductors, must be disconnected to retain the parallel paths. The Megger LT7 carries out an initial low current check to calculate what the contact voltage on accessible metalwork will be in a real fault. It must be less than 50V for the test to proceed.

To see many more Q & A in Voltimum UK's Experts Area, please click on the link:

http://www.voltimum.co.uk/consult.php?universe=consult.index.questions

 Related contacts
NAPIT
4th Floor, Mill 3, Pleasley Vale Business Park,
Mansfield, Nottinghamshire NG19 8RL
Tel: 0870 444 1392
Fax: 0870 444 1427
Email: info@napit.org.uk
Web: www.napit.org.uk
blue arrow pointing right   NAPIT

Source: N.A.P.I.T. & James Hunt
 Back

Related information

Related contacts

More News...

Q & A of the Day - Do I have to be approved to notify?
NAPIT's bright sparks
NAPIT's bright sparks
Q & A of the Day - Determination of insulation resistance
NAPIT response to hip consultation
NAPIT seminar at B&K Expo
NAPIT director appointed to TrustMark board
Free legal advice for NAPIT members