Q & A of the Day - Does a shower room light fitting have to be special?

2008-02-01
 Back
Intertek
 

Our Voltimum Experts answer your questions on a daily basis in our Technical Expertise area. This one, about whether a shower room light fitting needs to be a special one, is answered by ASTA BEAB Certification Services (now part of Intertek):

Question: Does a light fitting in a shower room have to be a vapour-proof fitting?

We are involved in managing disabled adaptations that are funded by Local Authority grants. To date we have always specified and had fitted vapour-proof light fittings, which the Local Authority has always paid for. We are now being told that they will not pay for these fittings. However, the electrical contractors are saying that if these fittings are not included, they will not issue the electrical certificate upon completion of their work. Can you confirm whether it is a requirement that vapour-proof light fittings be installed in a shower room?

Answer: Firstly, the term 'vapour-proof' is not a specified one. I am unsure of what you mean by 'vapour-proof'. If you are referring to the IP rating (moisture ingression rating) of the luminaire, then the IP rating must be adequate for the particular zone, see BS7671 Section 701. For example, Zone 2 would require at least an IPX4 rating. However, one aspect that is not specified is the use of an SELV luminaire directly above a shower. Although these can be fitted, they have a habit of the lamp exploding when sprayed with water. This is because the lamp face is exposed and hot. Many luminaire manufactures make specific products for this location that have an extra shield over the lamp. I would advise use of these directly above a shower.

To see many more Q & A in Voltimum UK's Experts Area, please click on the link:

www.voltimum.co.uk/consult.php?universe=consult.index.questions
pixel
Units showers may have their own lighting.
Units showers may have their own lighting.
pixel
A modern shower light.
A modern shower light.
pixel

 Back

 Related contacts
ASTA BEAB Certification Services (Intertek)
1 Station View, Guildford,
Surrey GU1 4JY
Tel: +44 (0)1483 455466
Fax: +44 (0)1483 455477
Email: info@astabeab.com
Web: www.astabeab.com
blue arrow pointing right   ASTA BEAB (Intertek)

 For latest electrical industry news, register for Voltimum's free newsletter.
Enter your email address here:
OK

Source: ASTA-BEAB (Intertek) & james Hunt

Related information

Related contacts

More News...

Q & A of the Day - Current ratings for bolts
Q & A of the Day - Part P and recessed downlights – why no fire hoods?
Q & A of the Day - Metal-cased AV equipment has 130V touch voltage – why?
Q & A of the Day – Temporary site lighting PAT
Q & A of the Day - Cloakroom lighting
Intertek acquires ASTA BEAB Certification Services
EMF & CE Marking