Q & A of the Day – Temporary site lighting PAT

2008-01-28
 Back
Intertek
 

Our Voltimum Experts answer your questions on a daily basis in our Technical Expertise area. This one, about whether, with temporary site lighting, the equipment needs portable appliance testing (PAT), is answered by ASTA BEAB Certification Services:

Temporary site lighting - needs PAT?
Temporary site lighting - needs PAT?
pixel
With Unistrut, this is temporary, not portable.
With Unistrut, this is temporary, not portable.
pixel
Question: I am part of the construction management team that is extending a chemical plant in Cumbria. I have instructed the electrical contractor to install some 110V fluorescent light fittings in a non-hazardous area. The method we have used is to install a supply and a four-way socket unit. The lights are then plugged into a socket. This makes them easy to move when we come up against pipe or equipment clashes.

The lights are clamped to steel work using Unistrut. They are temporary but not portable. Should the need to be moved arise, it would be the electrical contractor who would unplug it and reposition it.

If I understand the rules on portable equipment correctly, this type of installation is not classed as portable, and therefore would not require PAT. I would like your opinion please.

Answer: This installation is not portable but temporary. As the temporary installation is fitted by a qualified electrician, he should therefore conduct any necessary inspections and tests.

You stated that a four-way socket unit has been used for the supply. If this is a four-way extension lead with a plug on the end, then this is a portable item and will need PAT in its own right!

To see many more Q & A in Voltimum UK's Experts Area, please click on the link:

http://www.voltimum.co.uk/consult.php?universe=consult.index.questions

 Back

 Related contacts
ASTA BEAB Certification Services (Intertek)
1 Station View, Guildford,
Surrey GU1 4JY
Tel: +44 (0)1483 455466
Fax: +44 (0)1483 455477
Email: info@astabeab.com
Web: www.astabeab.com
blue arrow pointing right   ASTA BEAB

 For latest electrical industry news, register for Voltimum's free newsletter.
Enter your email address here:
OK

Source: ASTA BEAB & James Hunt

Related information

Related contacts

More News...

Q & A of the Day - Current ratings for bolts
Q & A of the Day - Part P and recessed downlights – why no fire hoods?
Q & A of the Day - Metal-cased AV equipment has 130V touch voltage – why?
Q & A of the Day - Does a shower room light fitting have to be special?
Q & A of the Day - Cloakroom lighting
Intertek acquires ASTA BEAB Certification Services
EMF & CE Marking