Can you explain how to carry out a voltage drop calculation on a cable?

FAQs Installation and Contracting
 
Find out here...

Answer:

The calculation for volt drop in a cable is carried out using the mV/A/m values from the voltage drop tables in Appendix 4 of BS 7671 for the type of cable in question.
The mV/A/m value is multiplied by the current carried and the length of the cable.

i.e. VD = mV/A/m x Ib x L where mV/A/m is taken from the
1000 appropriate table in Appendix 4
Ib = design current
L = length of cable in metres


Example:
Calculate the volt drop in a PVC sheathed 10mm2 cable supplying an 9kW single phase electric shower. The cable length is 20 metres.


VD = mV/A/m x Ib x L where mV/A/m = 4.4 from table 4D2B
1000 Ib = kW = 9000
Volts 230
VD = 4.4 x 39.13 x 20 Ib = 39.13A
1000
L = 20 metres
VD = 3.44Volts

Note: The maximum VD allowed is normally 4% of 230V = 9.2V


More News...

Is there a Regulation in BS 7671 which gives the minimum distance that a socket-outlet or other accessory can be installed near to a sink?
Can you explain the requirements of BS 7671 in relation to supplementary bonding in rooms containing a bath or shower?
Is it only items of equipment supplied via a 13amp plug that require to be tested during combined inspection and test of electrical appliances?
Can you explain the common earthing systems TN-S, TN-C-S and TT?
What is the correct course of action if a high earth fault loop impedance (Ze) value is measured at the origin of an existing supply?
In a TT system what are the requirements of BS 7671 in relation to the resistance of the earth electrode and the rated residual operating current of the RCD at the mains position.
What are your recommendations regarding the amount of inspection and testing that should be carried out during Periodic Inspection and Testing of an existing electrical installation?
This installation has BS 3036 rewireable fuses. Therefore, the consumer unit must be replaced by one containing circuit breakers.